Products

       At first from material and material supplier after a rigorous selection process, we choice all right         components for each items, we have advanced workshop, quality control system, specially custom         design engineers. OEM/ODM is welcome and can be done in donghua.
MODEL:HPSP-500 With PFC and Parallel Function Switching Power Supply

Features:
”¤ High efficiency, high reliability
”¤Universal AC input/ full range
”¤Built-in active PFC function, PF>0.95
”¤Protections: Short circuit/ Over load/ Over voltage/ Over    temperature
”¤Forced air cooling by built-in DC fan
”¤Current sharing up to 2000W(3+1)
”¤With power good and fail signal output
”¤Built-in remote ON-OFF control and remote sense function
”¤1 year warranty
”¤Dimensions: 278*127*63.5mm(L*W*H)



casing No. : H025

MODEL

HPSP-500
-5

HPSP-500-12

HPSP-500-13.5

HPSP-500 -15 HPSP-500 -24 HPSP-500 -27 HPSP-500 -48

OUTPUT

DC Voltage

5V

12V

13.5V

15V

24V

27V

48V

Voltage Tolerance

”Ą2.0%

”Ą1.0%

”Ą1.0%

”Ą1.0%

”Ą1.0%

”Ą1.0%

”Ą1.0%

Rated Current

80A

41.5A

37A

33A

20.8A

18.5A

10.5A

Current Range

0-80A

0-41.5A

0-37A

0-33A

0-20.8A

0-18.5A

0-10.5A

Rated Power

400W

498W

499.5W

495W

499.2W

499.5W

504W

Ripple & Noise

100mVp-p

150mVp-p

150mVp-p

150mVp-p

150mVp-p

150mVp-p

200mVp-p

DC Adjustment Range

-5%,+10%

-17%,+10%

”Ą11%

-10%,+20%

-17%,+10%

”Ą11%

-15%,+17%

Setup, Rise, Hold Time

1500ms,50ms,15ms at full load

INPUT

Voltage Range

90”«264 VAC 47-63Hz£»127”«370VDC

Power Factor

0.95/230VAC 0.98/100VAC at full load

AC Current

7A/115 VAC 3.5A/230VAC

Efficiency

76%

82%

82%

82%

84%

84%

86%

Inrush Current

Cold start 20A/115VAC 40A/230VAC

Leakage Current

<1mA/240VAC

PROTECTION

Over Load

110%~125%

Protection: Constant current limiting, recovers automatically after fault condition is removed

Over voltage

115%”«135%

Protection type: Shut down o/p voltage, re-power on to recover

Over Temp

RTH2”Ż95”ę (Detect on heatsink of Q1,Q7 power transistor & L3 output choke )

Protection type: Shut down o/p voltage, re-power on to recover

FUNCTION

Remote Control

RC+/RC£­:4 ~ 10VDC Power off, <0 ~ 0.8VDC Power on

ENVIRONMENT

Working Temp., Humidity

-10”ꔫ+60”ę£»20%”«90 %RH

Storage Temp., Humidity

-20”ꔫ+85”ę£»10%”«95 %RH

Vibration

10”«500Hz£¬2G 10min./1cycle, period for 60min, each along X, Y, Z axes

SAFETY

Withstand Voltage

I/P-O/P:3KVAC I/P-O/P:1.5KVAC O/P-FG: 0.5KVAC

Isolation Resistance

I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC

STANDARD

Safety Standard

Design refer to UL1950,TUV EN60950

EMC Standard

Design refer to EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11;ENV50204,EN55024

OTHERS

Weight

2.6Kg

Packing

6pcs/16Kg/1.14 CUFT

NOTE

1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25”ę of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12”åtwisted pair-wire terminated with a 0.1¦Ģ &47¦Ģ
   parallel capacitor.
3.Tolerance: includes set up tolerance, line regulation and load regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must
   be re-confirmed that it still meets EMC directives.