Products

       At first from material and material supplier after a rigorous selection process, we choice all right         components for each items, we have advanced workshop, quality control system, specially custom         design engineers. OEM/ODM is welcome and can be done in donghua.
LZZBW-10 Type Current Transformer
Applications

LZZBW-10 Type Current Transformer is intended for power measurement,current monitoring and relay protection in power system with rated frequency 50Hz or 60Hz and rated voltage 10kV.
Applicable Standard:IEC60044-1 Current transformer

Type Designation
Operation Conditions
Installation area: Outdoor.
Ambient temperature: Max. temperature 40íŠ;Min. temperature -5íŠ;Daily average temperature can't exceed 30íŠ.
Air conditions: No heavy pollution in air.
Technical Parameter
Model
Rated voltage radio
(kV)
Combined accuracy or Combined accuracy classes
Rated output
(VA)
ltimate output
(VA)
Rated insulation level
(kV)
LZZBW-10
5
0.2/10P10
0.5/10P10
0.2/10P15
0.5/10P15
10/15
10/15
10/15
15/15
0.45
1.125
10
0.9
2.25
15
1.35
3.375
20
1.8
4.5
30
2.7
6.75
40
3.6
9
50
4.5
11.25
75
6.75
16.875
100
9
22.5
150
13.5
33.75
200
18
45
300
24.5
61.25
400
24.5
61.25
500
32
80
600
32
80
800
32
80
1000
50
125
Structure and Feature
The transformer is of epoxy resin, hermetically sealed stucture with excellent insulated performance and anti-damp capacity.Outdoor used,it has unique outline and light weight.It's easy to clean it is surface.Four holes at the bottom of the CT are suitable for mounting.(There is a connection box in the secondary connection area)
Outline and Mounting Dimensions

Information Required for Order Placing
Model.
Rated voltage radio kV.
Combined accuracy classes and Rated output VA.
Altitude m.