LZZBJ9-12/185b/2(4) Type Current Transformer
Applications
LZZBJ9-12/185b/2(4) current transformer is suitable for power measurement, current monitoring and relay protection in power system with rater frequency 50Hz or 60Hz and rater voltage 10kV.
Applicable Standard: IEC60044-1, GB 1208 ¡¶Current transformer¡·.
Type Designation
Operation Conditions
Installation area: Indoor.
Ambient temperature: Max. temperature 40¡æ;Min. temperature -5¡æ;Daily average temperature can't exceed 30¡æ.
Air conditions: No heavy pollution in air.
Technical Parameter

Technical parameters of LZZBJ9-12/185b/2 Type Current Transformer
Model
Rated primary current
(A)
Combined accuracy classes
Rated output
(VA)
Rated short-time thermo current
(kA/s)
Rated dynamic stability current
(kA/s)
LZZBJ9-12/185b/2
5
0.2/10P10
0.5/10P10
0.2/10P15
0.5/10P15
10/15
10/15
10/15
15/15
0.75
1.875
10
1.5
3.75
15
2.25
5.625
20
3
7.5
30
4.5
11.25
40
6
15
50
7.5
18.75
75
11.25
28.125
100
15
37.5
150
22.5
56.25
200
30
75
300
0.2/10P10
0.5/10P10
0.2/10P15
0.5/10P15
10/15
10/15
10/20
15/20
45
112.5
400
45
112.5
500
45
112.5
600
45
112.5
800
0.2/10P10
0.5/10P10
0.2/10P15
0.5/10P15
15/20
15/20
15/20
30/20
100
250
1000
1200
1250
1500
0.2/10P10
0.5/10P10
0.2/10P15
0.5/10P15
15/20
15/20
20/20
30/20
140
350
2000
175
437.5
2500
3000
3150

Technical parameters of LZZBJ9-12/185b/4 Type Current Transformer
Model
Rated primary current
(A)
Combined accuracy classes
Rated output
(VA)
Rated short-time thermo current
(kA/s)
Rated dynamic stability current
(kA/s)
LZZBJ9-12/185b/4
5
0.2/0.2/5P10
0.2/0.5/5P15
0.2/0.5/5P20
0.2/5P10/10P15
0.5/5P10/10P20
10/10/20
10/10/15
10/10/15
10/15/15
10/15/15
0.75
1.875
10
1.5
3.75
15
2.25
5.625
20
3
7.5
30
4.5
11.25
40
6
15
50
7.5
18.75
75
11.25
28.125
100
15
37.5
150
22.5
56.25
200
30
75
300
0.2/0.2/5P10
0.2/0.5/5P15
0.2/0.5/5P20
0.2/5P10/10P15
0.5/5P10/10P20
10/10/20
10/10/20
10/15/15
10/15/20
15/15/15
45
112.5
400
500
600
0.2/0.2/5P10
0.2/0.5/5P15
0.2/0.5/5P20
0.2/5P10/10P15
0.5/5P10/10P20
10/10/20
10/10/15
10/10/15
10/15/15
15/15/15
45
112.5
800
50
125
1000
0.2/0.2/5P10
0.2/0.5/5P15
0.2/0.5/5P20
0.2/5P10/10P15
0.5/5P10/10P20
10/10/30
15/15/20
15/20/20
10/15/15
15/15/20
100
250
1200
1250
1500
140
350
2000
175
437.5
2500
0.2/0.2/5P10
0.2/0.5/5P15
0.2/0.5/5P20
0.2/5P10/10P15
0.5/5P10/10P20
15/15/30
15/15/20
15/20/20
15/15/20
15/20/15
175
437.5
3000
3150

Rated secondary current: 5A or 1A.
Rated insulation level£º12/42/75kV¡£
Structure and Feature
The Current transformer have the whole-sealed structure with epoxty resin as its main insulation. Its core adopts the crystallitic alloy or excellent silicon steel sheets to enwind becoming annular, then secondary leads are enwinded on it evenly. Primary conducts are winded by insulation belt to avoid short circuit between conducts. There are earth bolts and holes suitable for mounting on the bottom of the product suitable the mounting.
Outline and Mounting Dimensions
Information Required for Order Placing
Model.
Rated current ratio A.
Combined accuracy classes and Rated output VA.
Altitude m.