DGLH-1000¡«1600A Series Load Isolation Switch |
Service environment |
¡ôDGL load-isolation switch can operate under the following conditions;
¡ôAltitude not more than 2000m;
¡ôThe range of ambient temperature is from 5¡æ to 40¡æ;
¡ôRelative humidity not more than 95%;
¡ôThe environment without any explosive medium;
¡ôThe environment without any rain or snow attacking.
¡ôNote: If the product is expected to be used in the environment where temperature is over +40¡æ or below -5¡æ¡«-45¡æ, users shall tell it to the manufacturer. |
|
|
Type Designation |
AC 50Hz, rated voltage 660V, DC rated voltage 440V, rated current 1600A. It is used for making and breaking circuit infrequently. |
 |
Table |
One NO and one NC |
11 |
NO+NC |
Two NO and Two NC |
22 |
2NO+2NC |
Example for lectotype: Rated current 630A, include neutral pole transferring loadisolation switch, DGL Z-630A/4J for operating outside of cabinet
|
|
¡ô125~630A possesses three poles, and four pole ( three pole+onoff neutral pole).
¡ôObservation window can be provided for products below 630A can be provided according to the demand to observe directly the on and off state of the contact.
¡ôTwo set of auxiliary contacts can be assembled according to demand.
¡ôMechanical property and electric property correspond to the mechanical property and electric property of DGL-125~1600A.
¡ôNots: only offer products for operation outside board. |
|
|
Outline and Installation Size |

DGLH-1000¡«1600A/J Operation outside Base for installation |

1250¡«1600A Installation size of handle seat outside board
|
Type Specification |
External Dimension and Installation Dimension |
DGLH-1000¡«1600A |
A |
B |
J |
N |
R |
S |
T |
Y |
1000A/3 |
378 |
312 |
355 |
174 |
60 |
56 |
8 |
48 |
1000A/4 |
492 |
312 |
470 |
234 |
60 |
56 |
8 |
48 |
1250A/3 |
378 |
338 |
355 |
174 |
80 |
69 |
8 |
48 |
1250A/4 |
492 |
338 |
470 |
234 |
80 |
69 |
8 |
48 |
1600A/3 |
378 |
338 |
355 |
174 |
80 |
69 |
10 |
49 |
1600A/4 |
492 |
338 |
470 |
234 |
80 |
69 |
10 |
49 |
|
|
|